494 4 × 10 A Relay Unit
4-Channel Relay Unit (494)
The 4-Channel Relay Unit is a DALI-compatible interface unit designed to allow nondimmable loads to be incorporated into a DIGIDIM lighting control system. The relay unit is a DIN-rail mounted unit that can control four individually programmable relays. The relays are ‘normally open’, volt-free and can switch resistive loads of up to 10 A.
The relay unit is provided with a status LED, a physical selection switch and four relay state indicators. The status LED provides status and a fault indication. The physical selection switch is used to identify the device during system configuration and also acts as a manual override. The four relay state indicator LEDs are illuminated when the respective relay is closed.
Note: This unit does not contain a DALI power supply. Therefore, one must be present elsewhere in the system.
Key Features
- Four individually programmable relays, normally open and volt-free.
- Relays are internally isolated permitting separate phases to be controlled in one unit.
- Each relay can be manually controlled using the physical selection switch.
- All DALI functions are programmed with either DIGIDIM Toolbox or Designer software.
- DIN-rail mounted and only 88 mm wide.
Technical Data
Relay loads (max.)
|
Resistive:
|
10 A
|
Incandescent:
|
8 A
|
Inductive:
|
5 A
|
Electronic ballasts:
|
15 pcs Helvar Type EL–HF/CHF
|
Connections
|
DALI:
|
Solid core up to 4 mm²Stranded up to 2.5 mm²
|
DALI cable:
|
Removable connector blocksWire section: 0.5 mm² – 1.5 mm² stranded or solid core
|
Cable rating:
|
All cables must be mains rated. Note: If equipment is used in an electrically noisy environment, the DALI cable should be screened and connected to the earth.
|
Power
|
Mains supply:
|
220 VAC – 240 VAC50 Hz – 60 Hz
|
Mains supply output:
|
None
|
DALI consumption:
|
2 mA
|
Mechanical data
|
Dimensions:
|
88 mm × 58 mm × 90 mm
|
Housing:
|
DIN-rail case 88 mm wide
|
Weight:
|
300 g
|
Mounting:
|
DIN rail (installation in switchgear/controlgear cabinet)
|
IP code:
|
IP30
|
Operating and storage conditions
|
Ambient temperature:
|
0 °C to +40 °C
|
Relative humidity:
|
Max. 90 %, noncondensing
|
Storage temperature:
|
−10 °C to +70 °C
|
Conformity and standards
|
EMC emission:
|
EN 55015
|
EMC immunity:
|
EN 61547
|
Safety:
|
EN 61347-2-11
|
Isolation:
|
4 kV
|
Environment:
|