472 1–10 V / DSI Converter
472 DIGIDIM 1–10 V & DSI® Converter
The DIGIDIM 1–10 V & DSI® Converter has been designed to control electronic ballasts that comply with IEC 60929 and ballasts that comply with the DSI® standards. This ensures that DIGIDIM systems are compatible with, and easily integrated into, existing systems.
The Converter can switch a maximum of 15 Helvar electronic ballasts/drivers.
The analogue 1–10 V signal and the digital DSI® signal can control 50 electronic ballasts.
Key Features
- Out-of-box operation provides control using DALI standard broadcast commands.
- For 1–10 V control, the Converter can switch a maximum of 15 ballasts/drivers. An external contactor should be used for more ballasts.
- Converter complies with DSI® 1 and DSI® 2 standards.
- Default light output at initial power up is 100 %.
- Universal supply voltage operation.
- DIN-rail mounted and only 70 mm wide.
- Easy programming by using the group selection switch.
Additional Functions
- Controller status report.
- System failure level/Ignore.
- Power on to last level.
- Sink or source mode.
- /Min. levels, Fade times*, Scenes* and Groups*.
* These functions are programmable using a Helvar infrared remote control.
Technical Data
Connections
|
DALI:
|
Standard DIGIDIM removable terminal block 0.5 mm² – 1.5 mm² stranded or solid core
|
Mains:
|
Up to 4 mm² solid core or up to 2.5 mm² stranded
|
DSI® / 1–10 V:
|
Up to 2.5 mm²
|
Cable rating:
|
All cabling must be mains rated.
|
Power
|
Mains supply:
|
100 VAC – 240 VAC (nominal)85 VAC – 264 VAC (absolute)48 Hz – 62 Hz
|
Mains output:
|
10 A resistive, switched live
|
Load:
|
15 × EL-HFC ballasts/drivers(Use external contactor for additional ballasts)
|
External protection:
|
The mains supply must be protected at 10 A maximum. The relay must be protected by a 10 A Type C MCB maximum.
|
DALI consumption:
|
2 mA
|
Analogue output
|
Voltage range:
|
1 V – 10 V according to EN 60929
|
Sink current:
|
100 mA maximum
|
Number of devices:
|
50
|
Source mode current:
|
1.5 mA
|
DSI® output
|
Number of ballasts:
|
50
|
Compliance:
|
Complies with DSI® standard v 2.0
|
Mechanical data
|
Dimensions
|
70 mm × 58 mm × 90 mm
|
Housing:
|
DIN-rail case 70 mm wide
|
Mounting:
|
DIN rail (installation in switchgear/controlgear cabinet)
|
Weight:
|
140 g
|
IP code:
|
IP30 (IP00 at terminals)
|
Operating and storage conditions
|
Ambient temperature:
|
0 °C to +40 °C
|
Relative humidity:
|
Max. 90 %, noncondensing
|
Storage temperature:
|
−10 °C to +70 °C
|
Conformity and standards
|
EMC emission:
|
EN 55015
|
EMC immunity:
|
EN 61547
|
Safety:
|
EN 61347-2-11
|
Isolation:
|
3 kV mains to DALI3 kV mains to 1–10 V3 kV mains to DSI®1.5 kV DALI to 1–10 V & DSI®
|
Environment:
|
Complies with WEEE and RoHS directives.
|