Couldn't load pickup availability
Description
493 Signal Relay Unit
Single-Channel Signal Relay Unit (493)
The 493 is a single-channel relay unit, designed to allow interfacing with other building control and management systems.
The 493 signal relay unit is in a plastic enclosure, so it can be installed within a third-party equipment enclosure, electrical cabinet, or used as an in line unit. The relay is a solid-state, normally open signal relay, with a contact rating of 60 VAC or VDC, at a maximum of 0.5 A.
This unit must not be used to switch mains voltages. The unit is powered from the DALI network.
The compact enclosure has mounting lugs at each end, and cable grips are provided as part of the terminal cover.
The unit forms a DALI relay node with a typical current consumption of 10 mA, and is programmable as a single-channel relay by Helvar’s lighting design software, Designer and Toolbox.
Note: This unit does not contain a DALI power supply and therefore one must be incorporated elsewhere in the system.
Key Features
- Low power switching capability (0.1 mA to 0.5 A; 60 V)
- Solid state low-current relay
- Compact size for electrical panel or in-line mounting
- Secure wire connection cover
Installation Notes
- Remove the connection cover
- Connect the relay wires
- Connect the DALI control wires
- Secure the unit in place
Technical Data
Relay Contacts
Relay contacts: Normally open signal solid state relay (SSR)
Voltage: 60 VAC or VDC
Isolation: 4 kV
Maximum load: 0.5 A
Minimum load: 0.1 mA
Connections
DALI: 0.5 mm² – 1.5 mm² stranded or solid core
Strip length: 8.5 mm to 9.5 mm
DALI consumption: 10 mA
DALI cabling must be 230 V mains rated
Relay: 0.5 mm² – 1.5 mm² stranded or solid core
Strip length: 8.5 mm to 9.5 mm
Mechanical data
Dimensions: 118 mm × 40 mm × 21.2 mm
Housing: White plastic (polycarbonate)
Weight: 38 g
IP code: IP30
Operating and storage conditions
Ambient temperature: 0 °C to +40 °C
Relative humidity: Max. 90 %, non-condensing
Storage temperature: –10 °C to +70 °C
Conformity and standards
Emission: EN 55015
Immunity: EN 61547
Safety: EN 60950
Environment: Complies with WEEE and RoHS directives